Shi Hongjun Yang Yitao Zhang Henghua Shao Guangjie. Heat Transfer Coefficient of Cooling Water in Continuous Casting by Inverse Method. [J]. Special Casting & Nonferrous Alloys (9):528-530(2005)
Shi Hongjun Yang Yitao Zhang Henghua Shao Guangjie. Heat Transfer Coefficient of Cooling Water in Continuous Casting by Inverse Method. [J]. Special Casting & Nonferrous Alloys (9):528-530(2005)DOI:
Heat Transfer Coefficient of Cooling Water in Continuous Casting by Inverse Method
摘要
确定适当的冷却制度
尤其是对水冷换热系数的研究
对于提高连铸坯质量意义重大
为此
建立了铝合金连铸过程中喷水冷却换热系数的二维计算模型
采用试验测试铸坯冷却过程温度场和计算机模拟相结合的方法
可以比较准确地计算出冷却水的换热系数hα。结果表明
换热系数随着喷水量的增加而增大;随表面温度的升高呈先增后减的趋势。铸坯表面温度为50
5
50℃、喷水量为2.0
3
.8m3/h条件下
冷却水的换热系数hα=0.52(3759.61+24.39T-0.059T2)W0.94。
Abstract
Heat transfer coefficient of cooling water h
α
was calculated by experimental temperature field combining with simulated ones
in which estimated results of heat transfer coefficient of cooling water based on one-dimensional approximate difference method were employed by linear interpolation method.The results showed that heat transfer coefficient is increased with the augment of watering quantity
and earlier increased and then reduced with increase of surface temperature.The heat transfer coefficient h
α
is equal to (0.52(3 759.61+)24.39T-0.059T
2
)W
-0.94
under conditions of surface temperature of 50~550 ℃ and the cooling water of 2.0~3.8 m
3
/h.
关键词
连铸铝合金换热系数沸腾换热热流密度
Keywords
Continuous CastingAluminum AlloyHeat Transfer CoefficientBoiling Heat TransferHeat Flux